And If you’re interested in the podcast of live shows, here’s a link: https://rss.com/podcasts/he-hvac-guy-show In today's video, I'm going to a longtime customers house who had a couple of complaints, one of those was a loud noise when the system shuts off, and the other was that it didn't seem to be keeping up when the temperature is outside got above 90°. The loud noise was easy to diagnose and find, but the reason for her system not keeping up was actually quite complicated and it could've been multiple things I go through the diagnosis step-by-step to make sure that we fix it right the first time.
#hvacguy#hvac#airconditioning#airconditioner @ACIQComfort @MilwaukeeTool @BlueCollarWarrior @Onemanhvac @KoolinwithKrauss 00:00 Introduction 01:08 Noise Complaint Investigated and Explained 08:10 Checking Pressures 10:22 Finding Something Very Wrong 11:53 Hunting For And Eliminating Problems 14:30 Fixing Insulation, and Washing Coil 25:58 Ending And Final Diagnosis
Hey guys in the video I'm going to show you today,
the original call was because of a loud noise when the air conditioner shut off
and they happened to mention that it wasn't really keeping up very well.
Well the noise problem I quickly diagnosed and I'll show you exactly what it is but the reason
it was not keeping up was a difficult thing to diagnose. I'll admit I kind of knew what it was
as soon as I saw it but I walked through the steps of eliminating every other problem before
I decide what's wrong and what needs to be replaced. Stay tuned I think you'll like it.
What the customer is describing is a noise a bang it sounds like somebody's hitting the
hammer with hitting the air conditioner with a hammer when it shuts off. I have some real
good ideas about what that may be I've come across it several times and I'm going to hope
to catch it on camera so y'all can hear it and then hopefully show you what it is.
No sir um you can you can leave it on right now um yeah I'll take care of it.
Okay what I'm listening for when I push in the contactor is not necessarily a noise when it
starts but a noise when it shut shuts off listening specifically to this motor.
Okay that's the bang well it's not as loud as I thought it would be
so now we're going to kill the power and we're going to check on the motor and check for a
couple of things specifically. This is an older system like 15 years old this noise may not
explain why their system has not been keeping up but it is something that can normally be
fixed. Got all that shaking there's something first I want you to see something
y'all see that rust it's coming from between the blade and the hub that's my first sign that the
my idea of what might be wrong is correct. To test it is to see if the blade is actually
separating from the hub I'm going to grab the shaft that is hard to see actually I think
but this is moving the hub this hub right here with the screw in it is firmly attached to the
shaft so the blade and the hub should be one piece they're actually kind of stuck together
kind of like a rivet but right now if y'all see this it's moving just a little bit so the sound
is not coming from the motor but from the blade itself and it will eventually get so bad that
this will separate completely and it'll just bend. Okay what I want to explain the noise that
we heard when this system is turning when the fan is turning it has a lot of force in one direction
and then when it shuts off the weight of the blade and the sudden lack of
electromotive force turning the shaft causes the blade to put
a force in the other direction and that makes a boom when you hear it it hits with an impact
and if you allow it to continue to happen that impact will slowly make it worse and worse and
worse so we need to replace the whole blade. I'm going to go ahead and fire this thing back up
that blade is not bad enough to keep it from cooling and these customers complain that
it's not keeping up which tells me we probably got another problem
and like I said this thing's 15 years old and happens to be one of the first ones I ever installed
so this is a longtime customer here
I will mention that sometimes a motor can make that noise and and it's not the hub or the blade
a faulty motor can sometimes make a noise like that the motor not the hub so you always got
to check the hub first to eliminate it let's get this thing to come on while I'm waiting
on the time delay for the air conditioner to come on I'm going to go ahead and push in the
contactor again so y'all can hear this and understand what I'll maybe help understand
what I'm talking about that's what I was talking about that's the hub coming loose
from the blade at least in this case that's what it was it is not too uncommon to find something
like that let's wait on this to come on and we'll check pressures blown blown blown blown all right
I think we just I just heard it click so I think the thermostat has
just decided it's time to bring on the cooling
and this is somebody else down here I think the drain has gotten backed up and flooded the bottom
of the system that's why I can see some of this water it's not necessarily from rain
I don't know if y'all saw that but that was bubbling when I took the cap off the Schrader
valve was bubbling that's not good but if it is low on refrigerant that right there is an easy fix
thank you I would not say it's low on refrigerant um but that suction pressure looks really high
it's not but uh that makes me want to check temperature drop that suction pressure's
kind of high I'm expecting something more like 125 to 130.
yeah let me go in and check temp drop I'll be right back
yeah that suction pressure is still kind of high in my book that vapor saturation temperature is
kind of high I'll say let me get to my temp drop okay y'all see that is the difference between
those two outlets where y'all saw me put the um the probes it's going up slowly but I need a
temperature drop of something more like 14 or higher in order for this system to keep up
ideally you know textbook you're going to want something like 18 but when I'm measuring from the
filter to the register something like 18 is kind of really hard to achieve and in my opinion
if I'm getting something that high I'm going to start looking for airflow restriction
but if you're measuring just across the coil or at the back of the unit from the
return to the supply you might be able to get an 18 but that right there is really low
there are some things I'm wanting to check in here like superheat and subcooling
right now that uh suction line feels very cold I mean really cold
and my liquid line is right beneath that spinning fan blade so I have to be real careful if I'm
going to let it run and check it okay so I need to connect this on the other side of that txv
it doesn't have to be after that liquid line dryer but this ain't gonna be easy
tell you what let me take that off there we go that is my liquid line and I gotta tell
you this right here is hot you don't ever want to get your fingers caught in that fan blade
I have done it I have done it and I had to immediately go get stitched okay my temp drop
has increased to 10 that's better but this is something I wanted to look at
my sub cooling looks pretty good we have a txv head pressure don't look bad that
suction just looks really high and um that superheat is low
the low superheat makes me want to look at the evaporator coil so that's my next step
it is dirty although this is dirty man look at that look at that wheel
it looks worse than it is it's not built up terribly let me get a water hose we are going to
wash this out one thing I will notice is that the dog hair that y'all see has a line at the top and
that's because this insulation was folded down over the top of the coil so we need to clean the coil
and somehow make sure that doesn't happen before I wash off that coil this right here
and that little bit this is what was over the top of the coil and honestly glue is not going to work
and that's what it looks on the other side looks like on the other side
I got some more of these to do I'll show you when I'm done we got some extra screws in it
and this is the end result now see if I can get that where to adjust the light
let's work on that the drain pan is oh I got I got sludge coming out the drain pan
look at that I don't think it has drained in a while I don't know for sure
if we have resolved the problem enough to get our temp drop any higher I think it will definitely be
I would hope it would definitely be better but we're about to find out y'all don't let me forget
that my probes are in there now remember we already had a high suction my super heat should
do better but it is not I've got to let this run a while to see where my temp drop goes to
it's got to get a lot better than that this is my temp drop I'm still hovering around
nine and a half that might improve a little bit these are my pressures and temperatures
that pressure is a little bit high and this pressure is really high I would expect a
pressure like this if it were over 80 degrees in there okay so maybe we can get back to this
I think if I were overcharged this number right here my sub cooling would be high
that to me is a normal sub cooling none of this is normal though honestly if I
had a good reason for those pressures to be that high this saturation temperature should be
higher so now we need to look at TXV reversing valve and even the compressor
figure out why we're not getting the pressures and temperatures that we need
I have moved my temperature probes this is suction coming out of the evaporator
and I have put the other probe on true suction before it goes into the compressor there's only
probably about maybe a foot of pipe between the reversing valve and the compressor so what I'm
actually measuring is the difference in temperature between suction coming out of
the evaporator pull and suction going into the compressor and that is a check on the reversing
valve so let's look at it these are my two temperatures this is what's coming out of the
evaporator that's what's going into the compressor two degrees that is very acceptable to me
I think when you start getting around five or six you might have a problem
but just a little bit over two degrees like three degrees maybe that's pretty good so that's good
news it does not look like it is the reversing valve so we are zeroing in on why I have such a
suction and why my temp drop is only about 10 degrees not the reversing valve and
with this sub cooling I don't think it's low on refrigerant next thing I'm going to check is
make sure the compressor is pumping and by that the way I'm going to do that is very basic I'm
just going to check amp draw on the compressor and I'll share it with you that is 6.26 amps
that is kind of low my total amp draw is 8.97 which tells me I do not have a heat strip running
but that's 6.26 amps compressor my RLA is 13.5 that's about half of my RLA
truth is that's not too abnormal it is a little bit low but not sure at this point if my
txv which is one of the last things uh to check if it were restricted what in
holy smokes hold on just a second let's do it all right I have killed the breaker
that feeds the contactor over here if y'all will look at this this is a device installed
by the electric company to cause a time delay when when the power comes on and it is breaking
yellow for the time being I have bypassed this electric box its whole purpose is to cause a
time delay we have a time delay on the thermostat and on the board so um
between you and me I have a lot to do today my phone's ringing off the hook because it's hot
so I'm trying not to stress okay so I'm going to try to think this through with you
a little while ago I said if the txv were restricted I'd have a high superheat
that high suction pressure makes it obvious that the txv is not restricted
but the txv can be flooding the evaporator and that would give me a low superheat
it would create a higher suction pressure which might also reduce the amp draw on the compressor
a little bit if the compressor was not pumping that head pressure would not be that high
I know I'm gonna have some critics are gonna say I'm wrong but I'm gonna call this one the txv
I think it is stuck open and flooding the evaporator that's just my educated guess
I'm not perfect in my diagnosis but this one's kind of complicated and I think that's what the
correct answer is so I need to give her an estimate on a txv and a fan blade dryer and
four hours of labor it ain't gonna be cheap if y'all differ with my opinion
and you can back it up with some of these numbers please feel free to comment because
I don't just read them some of the new guys read them too and um it may be helpful to somebody