No cooling, not pumping to capacity.

HVAC GUY
26 followers
Tools I Use In My Videos 👇👇👇
https://www.amazon.com/shop/hvacguy
System’s compressor wasn’t pumping like it should. It sounded very noisy, and had very high suction, with low amp draw.
#hvac
#compressor
#hvaclife
The one I'm about to show you,
I apologize in advance for how noisy it is.
A couple times I tried to speak close to the microphone
so you could hear me.
But I tried to show the symptoms of a
compressor that is not pumping to capacity.
I couldn't show where I went inside,
but I did verify that it has a piston.
And the rest I'll try to show you in this video.
So my apologies for all the noise, but it's because of that compressor
as I'm on this
one because
The tenant here said times
the temperature can get up to 80 degrees
compressor
Stop it
We're documenting the compressor
not pumping to capacity.
The pressure is way too high
Okay,
so I
never
recovered
any, I
just
swapped
what
I was
reading
pressure
with,
the
pressure
actually looks normal, but that suction is way too hot,
I'm not sure if you can see it,
suction is at 205 and head pressure is at 262.
suction line temperature is 72 degrees
yeah i think we
were right the
first time this
is a compressor
that is failing
and not
pumping to
capacity