If you’re interested in more business related videos I’m starting to publish them for members. In time I plan on have a full selection on how to manage and complete every step of opening and running a business! Join this channel https://www.youtube.com/channel/UCiz21FXLOV65NTgiUfJsxTg/join
In today's video, I visited a customer that was complaining. The system was shutting on and off and on and off basically what we call short cycling. I investigated every possibility I could think of that would cause the system to short cycle and couldn't find anything. When I was fixing to leave and shutting the disconnect which was mounted in a very awkward way, I heard the blower shut off. I began to shake wires and wiggle things around, and inspect wire connections in the disconnect much more closely. And I found that the disconnect itself was the reason for the problem. In this particular case, there was a breaker feeding the entire air handler in the disconnect was not needed so I eliminated it and now there's no problem. I hope you enjoy.
This customer complains that the air conditioning,
not the heat, the air conditioning was cycling,
it was short cycling on and off and on and off and on and on.
So we just went in and turned it on, gonna watch it for a little while.
Stay tuned.
Man those
O-rings
go bad
so
fast.
Just need to select the correct
refrigerant
at 32.9
degrees.
We are running in cool right now.
Considering the temperatures right now,
that's not terrible.
Let me uh, I'm gonna check
superheat and subcooling.
I should still have a decent sub-cooling.
It's probably going to be hot.
Out here it's 52 degrees and it's 72 inside
and they want it colder.
I know what you're thinking.
Just open the window, right?
Okay, I have 9.5 degrees sub-cooling.
I hope y'all can see that.
And I'm still getting 8.8 degrees superheat.
I don't think I see anything with the pressures to make it short cycle.
So I'm going to...
kill the power and check
motors and capacitors
contactor all that good
stuff now i know there
was a screw in there
and look at here i just arrived
y'all see that let's see if i can get
it from over here
a drain right
in the way i think
the last time i
was out here we put
on this
capacitor that contactor looks clean there are
other things that can make it short cycle let's
go ahead and check this capacitor
specifically i'm thinking about the um
If it has a float switch
that could possibly do it.
That motor, the condenser fan motor,
made kind of a a little bit of a bang noise
when we turned it off and it was noisy the last time
we were out here. I'm checking for power.
Either either leg to ground and I've got nothing.
Shorten out to the fan,
shorten out
to the compressor.
You can
also short them to
ground. I do that just as a additional precaution.
Let's go ahead and check this.
All right, I cannot.
Okay, 70 and five is what that's supposed to be.
I was fixing to say I can't see what it is.
I just wasn't looking in the right spot.
Turned that to microfarads.
That one reads five, that is good.
And this one,
did y'all see that?
That said 4.8.
Man, I wish I knew where I bought this AMRAD.
Oh, hold on a second, that's completely different.
I got 67.6.
Maybe I just wasn't making a good connection.
That's not going to make it turn off
and it might even be within the range.
Plus ten percent minus five percent. So let's check it.
If I can find my calculator. All right
so take the rating and because
the lower limit is minus five
percent we're going to multiply that by 0.95
which subtracts that five percent. Seventy.
times 0.95 all right that is my lower limit
if it is above that that capacitor is good
so look and that was 66 point something
y'all are about to fall over there 67.6
so the capacitor is
good let's check
this motor up top that is
the railer magnet y'all
see me using yes it's in my
store and i'll
try to tag it
on the video
remember
first of all it
spins freely
that's good
I'm hearing just a little bit.
No.
What I'm doing is trying to shake it back and forth this way.
If it moves that way and makes a little clunk, the bearings are bad.
And it's not doing that.
Get one
of
these
sunk.
My air
handler
in the
attic.
I have already turned off the cooling.
It does have a float switch.
First, I just want to see
if there's any water.
I think
it's dry.
Nope, I don't feel any water.
I
don't
see
a
cover
in
here.
I can't get
to the...
Can't hardly get to this.
As it turns out,
that is not a very good place for that disconnect.
I just killed the power
because I don't want to cause it to destroy this insulation.
It may not be necessary
for what I want to do.
I just want to check this motor.
I guess I could have killed the power right here.
I'm doing
that same
thing with
the bearings.
Trying to rock the shaft back and forth.
I think the bearings are good.
Oh wow, I can't.
Right now I'm just looking
at those connections.
I can barely see because this thing
was not doesn't look like it was installed. The terminals
should
be coming out
over here instead
of over here.
Looks like blue
is on two
and maybe white is on five.
Because I don't have any room and I can't hardly
see it I'm gonna leave it right there for right now.
That right there that little grommet comes
inside new evaporator coils
so I know this coil has been replaced at least once.
Right now I am not really seeing a reason why
this thing would short cycle and it has been
kind of cold in the nights.
It's possible it happened during the heating mode. The customer
says they like it really cold
and there's no way they would have turned on the heat.
I don't know. I need to catch it when it's happening.
Whatever it was doing before it
is not doing it right now.
Okay when I plugged up the power it came on and then shut off.
I think we may
have found
our problem.
Let's look
in here a
little deeper.
Okay.
Everything
looks well
attached.
See if I can
see something.
All right. I
gotta find my
impact.
Here
it is.
So I'm in
here. I'm
going
to jump
down
where
you can
see.
Good
way to
put a
light on this.
I'm going to tighten up plugs all
the way around
and see if that helps. Wow. I got
a lot of turns out of that one.
Okay. Those are on loads.
I think it's going to matter if I tighten
those. Maybe a little bit.
It's time to go up top
and do this thing.
Are y'all hearing that? I'm
I'm hearing a snap.
I think we found our problem.
It is right here.
I saw a tiny little bit of spark and I heard it.
I'm trying to be very careful
not to throw sparks.
I have another disconnect in my van.
Let's go ahead and offer him that.
I think I found something.
Well, first of all, your wife's not crazy.
Okay.
I mean, she might be crazy, but...
Not with air conditioning, huh?
I need to see your breaker box.
It's right outside the garage.
All right um what I found was the disconnect up there was
not making a good connection
and I think we need to reconnect yourself.
Yes.
Forgive me I got a uh a mess of tools
so you're gonna have to hold on to mess as they say.
You ever get on the river with this thing?
Oh, yeah.
It's about to go hunt for the next two and a half weeks in Florida.
So I'm weird.
You talking about gator?
No, I hunt hogs.
Okay.
So I'm from the Florida panhandle, Panama City.
So I'll go home for Thanksgiving, and it'll stay there all winter.
And I'll go down to my parents' house,
and I'll just run to the river with it.
That's cool.
And take my kids hunting hogs and deer and everything else.
And then it'll sit.
All summer until we leave for July it'll sit
and then we'll go down to like Crystal River area
and we'll do all the shallow creeks
and all that stuff down there. Outside disconnect or
upstairs disconnect? Upstairs. Which one you want that AC breaker?
I think it's gonna be a big one
that's a 30 we're looking for something like a 50
or 60 it might say heat. There is a breaker
panel inside the house but I think it's up top left 60 amp that's it.
Alright, I need to replace your disconnect.
Okay, so the disconnect's bad.
Yes, even though I tighten the connections,
when I wiggle the wires, it will spark.
Oh, no, no, let's get it changed out.
And it'll cause the blower to stop.
That's why the blower, I keep hearing it kicking on and off.
That is it, that is it.
Okay, so she wasn't crazy, she found it.
Awesome possum, I like it.
I've got that in my house on my computer.
Yes, sir.
Oh, right.
That looks like my last disconnect
and it looks just like the one he's got.
Come on, let's do it.
I want to look
at this closely
and see there's
a tiny little bit
of arcing
right there. Maybe in a couple spots.
I don't know if it's just scratching. That
one little fork right
there looks like it
was arcing. This might
be a good time
to move this disconnect
because as y'all can see this is not exactly a good spot
for it. I might have something,
a grommet or something to put in there.
I brought
some Romex
connectors.
It didn't
give me a
lot of wire
to work with.
There we go.
All right there
is a little grommet
right here. Y'all hold
on just a second.
I didn't want to lose
this little grommet right here.
Oh my that looks like a half inch grommet. It might be. This is my
power wire. If I had some more number six
with me I could mount this right here but I used what I
had. I mean I could mount it back here on this wood
but I'm going to end up mounting it right
here.
I don't really see
anything in there
that would make
me think it
was shorting
but we saw it
So that doesn't look very healthy
does it? I do notice though
that the wire that was on that side
is darkened like it got hot.
You see the difference in color? This one looks copper
color that one looks more black. So I think that was our problem.
I'm gonna go ahead and pull this
out see about knocking
a hole right here.
Okay I now have the because
we have this breaker right
That serves as a disconnect.
And I've got a good mind to just eliminate that disconnect altogether
and just use the breaker.
That just seems to make most sense to me.
It passes code, and I think that's what I'm going to do.
They put that grounding lug in a place where I can just barely get
to it, so I'm going to move that too.
As you'll see, it is way up here.
Let's see if I can get this out.
Okay, now I can possibly get...
That is crazy
where that is.
It sure would
be nice
if I could get
on that.
I cannot.
I do have a few.
Other things
I can try.
There we go.
Okay now let's put
this back in here.
I can't see.
Y'all
hold on
just a
second.
There
we go.
All
good.
I'll
tell
you
what.
Let's
try to
knock
it
through
first.
Let me find
my hammer.
Excuse
my language.
I need
that other
one now.
Those
little
metal shards
are hot.
All right I'm
gonna leave
these screws
right here.
So uh makes it easy
to tighten them.
I'm gonna skin this
back a little bit.
That is good.
These basically need to be the same length,
so I'm going to cut this one right here.
This is number six. The strippers
on these only go up to number 10,
so I have to be very careful.
If y'all see me paying
a lot of attention
to my phone,
I'm waiting
on a phone call.
I don't want to cut
the copper underneath.
It's basically cut.
It's just not wanting
to come off.
There we
go. Go
ahead and
mount our
grounding
screw. A
self-tapper
to do it
though.
Straight in the back.
Alright, so that is now my ground lug.
Much easier to get to.
I didn't mean
to shake y'all
around like that.
Just
a little
bit more.
I'm going to move y'all where y'all can actually see what I'm doing.
Tighten it up.
There we go.
Alright, so now I'm going to shove that back in the corner.
I'm going to go ahead and tighten up.
Tighten up
these over here.
Because I've got
the insulation on the Romex.
I don't want it to pull out.
So I'm going to go ahead and tighten this up.
That's
enough.
You don't want it too tight.
Let me get that snug so it doesn't pull out any.
Okay, that is snug.
We'll tighten up again in just a second.
Now let's tighten it up.
We're good to go.
I say we go turn the power on and see what happens.
See what
happens.
That has
to be a more
secure way.
There's no real reason for an extra disconnect
if you've got a breaker right here.
And we just eliminated a possible problem.
I think we're good to go.
I'm getting ready to put stuff up.
I want to monitor this and listen to see if it slows down,
stops, or anything like that.
I still think we're good.
Guys, as y'all can see behind me, it's starting to get dark.
It is that time of year.
It's not but about 6 o'clock, so I got home late.
I normally don't work this late,
but I had a real doozy of a call late today,
and it made everything run behind.
I hope you enjoyed the video.
I did film something about Jobber that shows how easy it
is for me to add picture notes and voice
notes to a call and it I really like it
because it helps me sometimes when people call I do a
little bit of research before I call them back
or before I schedule the call I like to look back and
I can read the notes and see.
I mean I can even add pictures of the house,
I can add pictures of the model and serial numbers,
pictures of the equipment.
That way by the time I get there I am very familiar with that piece
of equipment and I like that.
If you like that idea there's a link for Jobber down in the
description. There's my buddy over there.
Y'all see him? He is thrilled to be outside. He's been
locked up for so long because there's construction going
on on the riverside. There's also a link
For ACIQ, my favorite equipment to install.
If y'all want to be an ACIQ dealer, use my link.
It does help me out, and it doesn't cost you anything different.
I hope you enjoyed the video.
If you did, how about like and subscribe?
Check out the store in the corner, and I'll catch you on the next one.