No power, eliminating all variables before finding problem.

HVAC GUY
27 followers
Tools I Use In My Videos 👇👇👇
https://www.amazon.com/shop/hvacguy
No cooling, no power, ohming out a compressor, ohming everything, finding loose lug on an oversized breaker.
#hvac
#electrical
#breaker
#repair
AI Generated·May contain errors
Video Summary
AI GeneratedA technician diagnoses an HVAC system that is not cooling despite the air handler running. After testing the compressor and checking for electrical shorts, the technician discovers a tripped 70-amp breaker caused by a loose connection. The technician replaces the oversized breaker with a safer alternative to prevent potential fire hazards.
Most of the day, it's been raining.
But it stopped long enough to check on this one.
It's calling for cooling inside.
Air handler's running, but nothing out here.
I hear what
sounds
like the
contactor
humming.
Let's see if it's...
All right, that's getting 24 volts.
I got no power.
Let's see if I can show you.
It's
calling.
No power.
We have had
something
trip
a breaker.
So let's go here and see if we got...
and go
to the
ground
lug
can
you
see
that
that's
9.3
mega
ohms
9.3
mega
ohms
we got
common
start
and run
this work
you can see
it past
experiences
are
telling me
to clean
a spot
right
there
first we're
going
to test
from here
to here
i got
nothing
nothing
now it's
showing
800 kilo ohms let
me finish ohming out
this compressor coming
to start 2.2 ohms coming to
run to it's like 0.7
so so run
the start we should
have something
like 32.6 it's
not perfect but it
should run and by the way
on these compressors
these lugs normally come
in two different
variations two on top and one on bottom like this one
and that's common start and then run on bottom
and sometimes it has one on top and two on bottom
and that's common start run but you can always
look in here
and find
out all
right we're
testing on
the ground
lug can you
see that 780
kilo ohms
i'm gonna try
something
real quick
let's omit
the ground
because
i'm still
showing nine
mega ohms
nine mega ohms nine
mega ohms to ground
that right there
showing me 400
kilo ohms to ground
and it's disconnected you see what i'm testing
that's my power lead 400 kilo ohms that one's
1.5 mega ohms
let's look
in that
disconnect
this is this
is supposed
to be
turned off
not sure i'm
gonna be
able to get
this we're ohming
the ground i
got nothing
nothing
nothing
check for
continuity
in this wire so we're gonna
swap this to that that's
my white wire that
continuity black
wire just not
understanding how
I got ohms to ground
okay now
I'm showing
nothing
and now I'm
showing
nothing
nothing
do I have it on
hold
or
something
180
kilo
ohms
to
ground
fried
looks
like
a
lizard
back
there
that shouldn't
have tripped
a breaker
those are not
touching let's
see if we
still got kilo ohms
to ground nothing all right sounds like
that condenser fan motor was giving
me my kilo ohms to ground
but i'll be honest i have never seen
well rarely have i seen a condenser
fan motor trip
a breaker we're
fixing to go look
for the breaker
and reset
this you see
which one's
tripped
a 70 amp
from
hawks
okay now
i got two
points
before
i hook
these
back up
nothing
okay
that
was a
70 amp
breaker
should
not
have
tripped
two
for
the
compressor
that
seems
a
little
high
it
was
that
breaker
it's
live
right
now
tight
oh
that
was
loose
i
think
it
was
just
a
loose
connection oh
that's hot smoke
what it was a
loose connection
that's got to be it
so
it's a
certain
it's
just
gonna
be a
loose
connection
measured
outside
to assume
that's aluminum.
70 amp breaker.
So I
recommended to
this homeowner
that we replace
that
breaker because I was afraid if something shorted outside
a 70 amp breaker might not trip and it
could start a fire.
So I recommended to her that we replace the breaker.
I had to go get it and I'm
on my way back over there to replace it.
I'll bring you along. I happen to know now that
An electrician did that right there.
I should have known better and put a 70-amp breaker on a condenser.
I had to get
this at
my shop
because it's
after hours.
I just happened to have one, and I knew I did.
And that right there,
no, is that number six?
I'm not sure.
Tighten those up a little bit.
Once I get it in place, I'll tighten them up some more.
I just don't want this
to fall out while I'm...
It looks like most of those are GE breakers.
I
feel
much
better
about
that.
It's
a
long
trip
around
for
a
breaker,
but
we
found
the
problem.
Prevented more serious problems.